Fluke 1623-2 GEO Earth Ground Resistance Meter
Fluke 1623-2 Basic Geo Earth Ground Tester at Tools Bangladesh. This reliable product easily uses to the workplace. Buy now for free delivery...
Model: Fluke 1623-2 GEO Earth Ground Resistance Meter
Fluke 1623-2 GEO earth tester Performs stakeless earth ground rod testing (two clamps). One of the most important things about Fluke 1623-2 earth tester always provides accurate results in any environment.
Fluke Earth Ground Tester performs all four ground tests quickly and accurately. This tester has automatic Frequency Control that identifies existing interference and chooses a measurement frequency to minimize its effect, thus providing a more accurate earth ground value.
This is not only provie accurate results. the value of this product exposes to the work spot. So, use to easily buy form Tools Bangladesh.
Fluke 1623-2 GEO Earth Ground Resistance Meter
Key Features:
- A unique earth ground tester that performs fast, accurate testing with and without stakes
- Tests 3- and 4-pole fall-of-potential, and 4-pole soil resistivity (with stakes)
- Performs selective earth ground rod testing (one clamp + stakes)
- Performs stakeless earth ground rod testing (two clamps)
- Features IP56 rating for outdoor use
Specifications: Fluke 1623-2 GEO Earth Ground Resistance Meter
General Specifications | |
Display: 1999 digit LCD | Display with special symbols, digit height 25 mm, fluorescent backlight |
User interface | Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button |
Robust, water and dust resistant | Instrument is designed for tough environmental conditions (rubber protective cover, IP56) |
Memory | Internal memory storage up to 1500 records accessible via USB port |
Temperature Range | |
Operating temperature | -10°C to 50°C (14°F to 122°F) |
Storage temperature | -30°C to 60°C (-22°F to 140°F) |
Temperature coefficient | ±0.1% of reading/°C < 18°C > 28°C |
Intrinsic error | Refers to the reference temperature range and is guaranteed for 1 year |
Operating error | Refers to the operating temperature range and is guaranteed for 1 year |
Climatic class | C1 (IEC 654-1), -5°C to +45°C (23° to +115° F), 5% to 95% RH |
Protective type | IP56 for case, IP40 for battery door according to EN60529 |
Safety | Protection by double and/or reinforced insulation. max. 50 V to earth. IEC61010-1: Pollution degree 2 |
EMC (emission immunity) | IEC61326-1: Portable |
Quality system | Developed, designed and manufactured according to DIN ISO 9001 |
External voltage | V ext, max = 24 V (DC, AC < 400 Hz), measurement inhibited for higher values |
V ext rejection | > 120 dB (162⁄3, 50, 60, 400 Hz) |
Measuring time | Typical 6 seconds |
Max. overload | 250 V rms (pertains to misuse) |
Auxiliary power | 6 x 1.5 V Alkaline (type AA LR6) |
Battery life span | Typical > 3,000 measurements |
Dimensions (W x H x D) | 250 x 133 x 187 mm (9.75 x 5.25 x 7.35 in) |
Weight | 1.1 kg (2.43 lb) including batteries 7.6 kg (16.8 lb) incl. accessories and batteries in carrying case |
RA 3-Pole Ground Resistance Measurement (IEC 1557-5) | |
Switch position | RA 3-pole |
Resolution | 0.001 Ω to 10 Ω |
Measuring range | 0.020 Ω to 19.99 kΩ |
Accuracy | ±(2% rdg + 3 d) |
Operating error | ±(5% rdg + 3 d) |
Measuring Principle: Current/Voltage Measurement | |
Measuring voltage | Vm = 48 V AC |
Short-circuit current | > 50 mA |
Measure frequency | 128 Hz |
Probe resistance (RS) | Max 100 kΩ |
Auxiliary earth electrode resistance (RH) | Max 100 kΩ |
Additional error from RH and RS | RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2% |
Monitoring of RS and RH with error indicator. Automatic range selection. Measurement is not performed if the current through the current clamp is too low. |
|
RA 4-Pole Ground Resistance Measurement (IEC 1557-5) | |
Switch position | RA 4-pole |
Resolution | 0.001 Ω to 10 Ω |
Measuring range | 0.020 Ω to 19.99 kΩ |
Accuracy | ±(2% rdg + 3 d) |
Operating error | ±(5% rdg + 3 d) |
Measuring Principle: Current/Voltage Measurement | |
Measuring voltage | Vm = 48 V AC |
Short-circuit current | > 50 mA |
Measure frequency | 128 Hz |
Probe resistance (RS + RES) | Max 100 kΩ |
Auxiliary earth electrode resistance (RH) | Max 100 kΩ |
Additional error from RH and RS | RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2% |
Monitoring of RS and RH with error indicator. Automatic range selection. |
|
RA 3-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp ) | |
Switch position | RA 3-pole with clamp |
Resolution | 0.001 Ω to 10 Ω |
Measuring range | 0.020 Ω to 19.99 kΩ |
Accuracy | ±(7% rdg + 3 d) |
Operating error | ±(10% rdg + 5 d) |
Measuring Principle: Current/Voltage Measurement (with External Current Clamp) | |
Measuring voltage | Vm = 48 V AC |
Short-circuit current | > 50 mA |
Measure frequency | 128 Hz |
Probe resistance (RS) | Max 100 kΩ |
Auxiliary earth electrode resistance (RH) | Max 100 kΩ |
Monitoring of RS and RH with error indicator. Automatic range selection. Measurement is not performed if the current through the current clamp is too low. |
|
RA 4-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp ) | |
Switch position | RA 4-pole with clamp |
Resolution | 0.001 Ω to 10 Ω |
Measuring range | 0.020 Ω to 19.99 kΩ |
Accuracy | ±(7% rdg + 3 d) |
Operating error | ±(10% rdg + 5 d) |
Measuring Principle: Current/Voltage Measurement (with External Current Clamp) | |
Measuring voltage | Vm = 48 V AC |
Short-circuit current | > 50 mA |
Measure frequency | 128 Hz |
Probe resistance (RS) | Max 100 kΩ |
Auxiliary earth electrode resistance (RH) | Max 100 kΩ |
Monitoring of RS and RH with error indicator. Automatic range selection. Measurement is not performed if the current through the current clamp is too low. |
|
Stakeless Ground Loop Measurement (2 Clamps) | |
Switch position | RA 4-pole 2 clamps |
Resolution | 0.001 Ω to 10 Ω |
Measuring range | 0.020 Ω to 19.99 kΩ |
Accuracy | ±(7% rdg + 3 d) |
Operating error | ±(10% rdg + 5 d) |
Measuring Principle: Stakeless Measurement of Resistance in Closed Loops Using Two Current Transformers | |
Measuring voltage | Vm = 48 V AC |
Measure frequency | 128 Hz |
Noise current (IEXT) | Max. IEXT = 10 A (AC) (RA < 20 Ω) |
Max. IEXT = 2 A (AC) (RA > 20 Ω) | |
Automatic range selection. The information regarding stakeless ground loop measurements is only valid when used in conjunction with the recommended current clamps at the minimum distance specified. |
Fluke 1623-2 GEO Earth Ground Resistance Meter
Includes:
- GEO Earth Ground Tester
- User's Manual
- Batteries
- Quick Reference Guide
- 2 Test Leads
- USB Cable
Accessories: Fluke 1623-2 GEO Earth Ground Resistance Meter
Kits (2)
- Fluke ES-162P3-2 3-Pole Stake Kit
- Fluke ES-162P4-2 4-Pole Stake Kit
Cables (3)
- Fluke Cable Reel 25M BL
- Fluke Cable Reel 25M GR
- Fluke Cable Reel 50M RD
Current clamps (1)
- Fluke EI-1623 Selective/Stakeless Clamp Set
Other (3)
- Fluke EI-162AC Clip-on Current Transformer (Inducing)
- Fluke EI-162BN 320 mm Diameter Split Core Transformer
- Fluke EI-162X Clip-on Current Transformer (Sensing) with Shielded Cable Set