Kyoritsu KEWMATE 2000A Digital Multimeter with analog bar and current pliers with open clip for cable diameter up to 6 mm. AC/DC Digital Multimeter with an open-jaw current clamp.
3400-count LCD with bar graph display AC and DC current measuring capability with open-jaw sensor Pocket-sized with heavy-duty case design. Auto-ranging, with data-hold and range-hold functions. Sleep function to save battery consumption.
Key Features: Kyoritsu KEWMATE 2000A Digital Multimeter
• Capable of measuring AC and DC currents up to 60A with OPEN CLAMP SENSOR.
• 3400 counts with bar graph display.
• Pocket size and heavy-duty design.
Specifications: Kyoritsu KEWMATE 2000A Digital Multimeter
| DC V |
340.0mV/3.400/34.00/340.0/600V (Input Impedance: 10MΩ) ±1.5%rdg±4dgt |
| AC V |
3.400/34.00/340.0/600V (Input Impedance: 10MΩ) ±1.5%rdg±5dgt [50 - 400Hz] |
| DC A |
60.0A ±2%rdg±5dgt |
| AC A |
60.0A ±2%rdg±5dgt (50/60Hz) |
| Ω |
340.0Ω/3.400/34.00/340.0kΩ/3.400/34.00MΩ ±1%rdg±3dgt (0 - 340kΩ) ±5%rdg±5dgt (3.4MΩ) ±15%rdg±5dgt (34MΩ) |
| Continuity buzzer |
Buzzer sounds below 30±10Ω (Continuity buzzer works on 340Ω range only) |
| Frequency |
(AC A) 3.400/10.00kHz ±0.1%rdg±1dgt (AC V) 3.400/34.00/300.0kHz ±0.1%rdg±1dgt (Input sensitivity Current: more than 15A, Voltage: more than 30V) |
| Conductor size |
Ø6mm max. |
| Applicable standards |
IEC 61010-1 CAT III 300V, CAT II 600V Pollution degree 2 IEC 61010-031, IEC 61010-2-032, IEC 61326-1, EN 50581(RoHS) |
| Power source |
R03 (AAA)(1.5V) × 2 * Continuous measuring time: approx. 45 hours (Auto power save: approx. 10 minutes) |
| Dimensions |
128(L) × 87(W) × 24(D)mm |
| Weight |
210g approx. (including batteries) |
| Included Accessories |
R03 (AAA) × 2, Instruction Manual |
| Optional Accessories |
9107 (Carrying case [Soft]) |