Model: Fluke 381 Remote Display True RMS Clamp Meter with iFlex
Fluke 381 Remote Display True RMS Clamp Meter with iFlex. Now one technician can do jobs that would otherwise require two people. Clamp the Fluke 381 around a conductor, remove the display and walk across the room to operate controls or remove protective equipment, all while watching real-time readings.
The iFlex® of Fluke is Flexible Current Probe (included) expands the measurement range to 2500 A AC while providing increased display flexibility. With a cord that runs 6 feet, you can finally measure those tight spaces, awkward sized conductors and disorganized wires.
Limited stock at Tools Bangladesh as soon as possible get out it otherwise You will never find it from another one.
Fluke 381 Remote Display True RMS AC/DC Clamp Meter with iFlex®
Key features
- Wireless technology allows the display to be carried up to 30 ft. away from the point of measurement for added flexibility without interference with measurement accuracy
- The removable magnetic display can be conveniently mounted where it is easily seen
- iFlex® Flexible Current Probe expands the measurement range to 2500 A AC
- CAT IV 600 V, CAT III 1000 V
- Integrated low pass filter and state-of-the-art signal processing allows for use in noisy electrical environments while providing stable readings
- Proprietary inrush measurement technology to filter out noise and capture motor starting current exactly as the circuit protection sees it
- Ergonomic design fits in your hand and can be used while wearing protective equipment
- Radio transmitter automatically sets the correct measurement range so you do not need to change the switch positions while taking a measurement
- Three-year warranty
- Soft carrying case
Safety Conformance
- IEC/EN 61010-1:2001, 1000V CAT III, 600V CAT IV
Specifications: Fluke 381 Remote Display True RMS AC/DC Clamp Meter
| Electrical Specifications |
| AC Current via Jaw |
| Range |
999.9 A |
| Resolution |
0.1 A |
| Accuracy |
2% ± 5 digits (10-100 Hz)
5% ± 5 digits (100-500 Hz) |
| Crest Factor (50/60 Hz) |
3 @ 500 A
2.5 @ 600 A
1.42 @ 1000 A
Add 2% for C.F. > 2 |
| AC Current via Flexible Current Probe |
| Range |
999.9 A / 2500 A (45 Hz – 500 Hz) |
| Resolution |
0.1 A / 1 A |
| Accuracy |
3% ± 5 digits |
| Crest Factor (50/60 Hz) |
3.0 at 1100 A
2.5 at 1400 A
1.42 at 2500 A
Add 2% for C.F. > 2 |
| Position Sensitivity |
 |
Distance from Optimum |
| |
i2500-10 Flex |
i2500-18 Flex |
Error |
| A |
0.5 in (12.7 mm) |
1.4 in (35.6 mm) |
±0.5% |
| B |
0.8 in (20.3 mm) |
2.0 in (50.8 mm) |
±1.0% |
| C |
1.4 in (35.6 mm) |
2.5 in (63.5 mm) |
±2.0% |
| Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature range. |
| DC Current |
| Range |
999.9 A |
| Resolution |
0.1 A |
| Accuracy |
2% ± 5 digits |
| AC Voltage |
| Range |
600 V /1000 V |
| Resolution |
0.1 V / 1 V |
| Accuracy |
1.5% ± 5 digits (20 – 500 Hz) |
| DC Voltage |
| Range |
600.0 V /1000 V |
| Resolution |
0.1 V / 1 V |
| Accuracy |
1% ± 5 digits |
| Frequency – Via Jaw |
| Range |
5.0 – 500.0 Hz |
| Resolution |
0.1 Hz |
| Accuracy |
0.5% ± 5 digits |
| Trigger Level |
5 – 10 Hz, ≥ 10 A
10 – 100 Hz, ≥ 5 A
100 – 500 Hz, ≥ 10 A |
| Frequency via Flexible Current Probe |
| Range |
5.0 to 500.0 Hz |
| Resolution |
0.1 Hz |
| Accuracy |
0.5% ± 5 digits |
| Trigger Level |
5 to 20 Hz, ≥ 25 A
20 to 100 Hz, ≥ 20 A
100 to 500 Hz, ≥ 25 A |
| Resistance |
| Range |
600 Ω/6 kΩ/60 kΩ |
| Resolution |
0.1 Ω/1 Ω/10 Ω |
| Accuracy |
1% ± 5 digits |
| Mechanical Specifications |
| Size (L x W x H) |
277 x 88 x 43 mm (55 mm for remote unit) |
| Weight |
350 g |
| Jaw Opening |
34 mm |
| Flexible Current Probe Diameter |
7.5 mm |
Flexible Current Probe Cable Length
(head to electronics connector) |
1.8 m |
| Environmental Specifications |
| Operating Temperature |
-10°C to +50°C |
| Storage Temperature |
-40°C to +60°C |
| Operating Humidity |
Non condensing (< 10°C)
≤ 90% RH (at 10°C to 30°C)
≤ 75% RH (at 30°C to 40°C)
≤ 45% RH (at 40°C to 50°C)
(Without Condensation) |
| Operating Altitude |
2,000 meters |
| Storage Altitude |
12,000 meters |
| EMI, RFI, EMC, RF |
EN 61326-1:2006, EN 61326-2-2:2006
ETSI EN 300 328 V1.7.1:2006
ETSI EN 300 489 V1.8.1:2008
FCC Part 15 Subpart C Sections 15.207, 15.209, 15.249
FCCID: T68-F381
RSS-210 IC: 6627A-F381 |
| Temperature Coefficients |
Add 0.1 x specified accuracy for each degree C above 28°C or below 18°C |
| Wireless Frequency |
2.4 GHz ISM Band 10 meter range |
| Safety Compliance |
ANSI/ISA S82.02.01:2004
CAN/CSA-C22.2 No. 61010-1-04
IEC/EN 61010-1:2001 to 1000V CAT III, 600V CAT IV. |
| Double Insulation Clearance |
Per IEC 61010-2-032 |
| Double Insulation Creepage |
Per IEC 61010-1 |
| Agency Approvals |
Fluke 381 Remote Display True RMS AC/DC Clamp Meter with iFlex®
Includes:
- 18-inch iFlex®flexible current probe
- Coated instruction card
- Safety information sheet
- Soft carrying case
- TL75 test leads
- Five AA Alkaline batteries
Accessories: Fluke 381 Remote Display True RMS AC/DC Clamp Meter with iFlex®
Cases (2)
- C345 Soft Carrying Case
- Fluke C550 Tool Bag
Clips (3)
- Fluke AC220 SureGrip™ Alligator Clips
- Fluke AC87 Heavy Duty Bus Bar Clip Set
- Fluke AC89 Heavy Duty Insulation Piercing Test Clip
Lights (2)
- Fluke LVD1A Non-Contact Voltage Tester with LED Flashlight
- Fluke L206 Deluxe LED Hat Light
Current probes (1)
- Fluke i2500-10 iFlex® Flexible Current Probes
Test leads (3)
- Fluke TL75 Hard Point™ Test Lead Set
- Fluke TLK289 - Industrial Master Test Lead Set
- Fluke TL175 TwistGuard™ Test Leads
Test probes (1)
- Fluke TP1 Slim Reach Test Probes
Write a Review